UFC 3-580-10
14 July 2004
Including changes 12 April 2005
DPOP 19 & 20- Redundant Small Base (34 To 85 Seats) [Two- 1-Ton A/C unit - Preferred ]
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
Wire Size
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
NORMAL
18
25
20
20
38
45
70/2
3#4, #8 G, 1"C
12,600
120/208/1 PH.
UPS FAILURE
26
8
20
20
46
28
DPOP 19 & 20- Redundant Small Base (34 To 85 Seats) [One- 2-Ton A/C unit - Alternate]
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Wire Size
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
NORMAL
18
15
20
20
38
35
70/2
3#4, #8 G, 1"C
12,600
120/208/1 PH.
UPS FAILURE
26
8
20
20
46
28
DPOP 24 & 25 Redundant Small Base -EXT. UPS-Two-1 Ton A/C Preferred
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Wire Size
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
50/2
3#8, #10 G, 1"C
12,602
NORMAL
8
8
20
20
28
28
55