UFC 3-580-10
14 July 2004
Including changes 12 April 2005
Table D-1 -- Point of Presence (POP)
Large Base No Server Farm (450 to 1700 Seats)- 208 V POWER FEED
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
FEEDERS
COOLING
Heat to
EQUIPMENT
BK
Wire Size
(VOLT/Phase)
Phase A/B/C
Phase A/B/C
Phase A/B/C
Room
AMP/POLE
(Btu/hr)
208Y/120 3PH
94
UPS 1
-
94
175A/3P
4#2/0, #6G, 2"C
208Y/120 3PH
6
UPS 2
-
6
175A/3P
4#2/0, #6G, 2"C
208Y/120 3PH
-
70
A/C #1
70
150A/3P
3#3, #8 G, 1"C
114,087
208Y/120 3PH
-
70
A/C #2
70
150A/3P
3#3, #8 G, 1"C
3-500KCM,1-
SINGLE SITE FEEDER:
239
350A/3P
3/0N,#1 G, 3-1/2"C
Large Base No Server Farm (450 to 1700 Seats)-480 V POWER FEED
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
FEEDERS
COOLING
Heat to
EQUIPMENT
BK
Wire Size
(VOLT/Phase)
Phase A/B/C
Phase A/B/C
Phase A/B/C
Room
AMP/POLE
(Btu/hr)
480V 3PH
42
-
42
UPS 1
80A/3P
4#2/0, #6G, 2"C
480V 3PH
2
-
2
UPS 2
80A/3P
4#2/0, #6G, 2"C
480V 3PH
-
36
36
A/C #1
60A/3P
3#3, #8 G, 1"C
117,141
480V 3PH
-
36
36
A/C #2
60A/3P
3#3, #8 G, 1"C
3-2/0, #6 G, 1-
SINGLE SITE FEEDER:
116
175A/3P
1/2"C
52