UFC 3-580-10
14 July 2004
Including changes 12 April 2005
DPOP 5 & 6 Redundant Medium Base - (251 to 449 Seats)- (Two - One Ton A/C units)
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Wire Size
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
NORMAL
20
17
20
20
40
37
70/2
3#4, #8 G, 1"C
13,859
120/208/1 PH.
UPS FAILURE
10
27
20
20
30
47
DPOP 14 & 15 Redundant Medium Base - (251 to 449 Seats)-EXT. UPS(Two- 1 ton A/C units)
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
Wire Size
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
50/2
3#8, #10 G, 1"C
12,403
NORMAL
14
15
20
20
34
35
DPOP3 & 7 Redundant Small Base_2 (86 to 250 Seats) [Two 1-Ton A/C units - Preferred]
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
Wire Size
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
NORMAL
23
20
20
20
43
40
70/2
3#4, #8 G, 1"C
15,918
120/208/1 PH.
UPS FAILURE
33
10
20
20
53
30
53