UFC 3-580-10
14 July 2004
Including changes 12 April 2005
DPOP 3 & 7 Redundant Small Base_2 (86 to 250 Seats) [One 2-Ton A/C unit - Alternate]
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
Wire Size
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
NORMAL
23
20
17
17
40
37
70/2
3#4, #8 G, 1"C
15,918
120/208/1 PH.
UPS FAILURE
33
10
17
17
50
27
DPOP 12 & 13 Redundant Small Base_2 (86 to 250 Seats) [One 2-Ton A/C unit - Alternate] -EXT. UPS
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Wire Size
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
50/2
3#8, #10 G, 1"C
12,195
NORMAL
14
13
17
17
31
29
DPOP 12 & 13 Redundant Small Base_2 (86 to 250 Seats) [Two 1-Ton A/C unit - Preferred] -EXT. UPS
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Wire Size
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
50/2
3#8, #10 G, 1"C
12,195
NORMAL
14
13
20
20
34
33
54