UFC 3-580-10
14 July 2004
Including changes 12 April 2005
DPOP 1-Non-Redundant Small Site (1 to 16 Seats) [One 2-Ton A/C unit - Alternate]
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
Wire Size
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
NORMAL
16
14
17
17
33
31
50/2
3#8, #10 G, 1"C
11,406
120/208/1 PH.
UPS FAILURE
30
-
17
17
47
17
Cabinet 'WPOP10'(SEAT COUNT LESS THAN 24)
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Wire Size
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
50/2
3#8, #10 G, 1"C
3,296
NORMAL
3
3
3
3
6
6
Cabinet 'WPOP21'(SEAT COUNT 1-21)- VSS -uTB(COI)
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Wire Size
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
50/2
3#8, #10 G, 1"C
1,072
NORMAL
3
-
-
3
3
3
Cabinet 'WPOP21'(SEAT COUNT 1-21)- VSS-uTBa
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
Wire Size
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
50/2
3#8, #10 G, 1"C
621
NORMAL
2
-
-
3
2
3
59