UFC 3-580-10
14 July 2004
Including changes 12 April 2005
DPOP17 SERVER CABINET 2 (1701 to 5000 Seats) [One 2-Ton A/C unit ]
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
Wire Size
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
NORMAL
33
18
17
17
50
35
100/2
3#3, #8 G, 1"C
18,535
120/208/1 PH.
UPS FAILURE
49
2
17
17
66
19
DPOP 16& 17 -SERVER CABINETS (1701 to 5000 Seats) [Two 2-Ton A/C unit ] -EXT.UPS
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
(VOLT/Phase)
Phase A/B/C
Phase A/B/C
Phase A/B/C
Wire Size
Room
AMP/POLE
(Btu/hr)
208Y/120 3 PH
125/2
4#1, #6 G, 1.5"C
32,972
NORMAL
31
65
96
61