UFC 3-580-10
14 July 2004
Including changes 12 April 2005
Table D-2 Main Cross Connect
Main Cross Connect - Without Cooling Equipment
VOLT
CABINET EQUIPMENT AMPS *
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
SEAT CNTS
CABINET
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A Phase B
BK AMP/POLE
Wire Size
Heat to Room
(Btu/hr)
DMDF1
< 96
120/208/1 PH.
18
16
0
0
18
16
30/2
3#10, #10G, 3/4"C
10,915
DMDF2
< 64
120/208/1 PH.
12
10
0
0
12
10
30/2
3#10, #10G, 3/4"C
7,197
DMDF3
< 64
120/1 PH.
11
9
0
0
11
9
30/2
3#10, #10G, 3/4"C
7,197
DMDF4
< 64
120/1 PH.
10
7
0
0
10
7
30/2
3#10, #10G, 3/4"C
6,331
DMDF5
< 60
120/208/1 PH.
10
7
0
0
10
7
30/2
3#10, #10G, 3/4"C
6,189
DMDF6
< 128
120/208/1 PH.
19
17
0
0
19
17
40/2
3#8, #10G, 3/4"C
6,331
DMDF6 (UPS Fault)
< 128
120/208/1 PH.
27
9
0
0
27
9
40/2
3#8, #10G, 3/4"C
13,848
DMDF7
<64
120/208/1 PH.
12
12
0
0
12
12
30/2
3#10, #10G, 3/4"C
7,750
DMDF8
<0
-
-
-
-
-
-
-
-
-
-
SMDF9
<60
120/1 PH.
13
8
0
0
13
8
30/2
3#10, #10G, 3/4"C
6,192
DMDF10
<128
120/208/1 PH.
26
24
0
0
26
24
40/2
3#8, #10G, 3/4"C
11,632
DMDF11
120/208/1 PH.
2
3
0
0
2
3
30/2
3#10, #10G, 3/4"C
2,258
DMDF12
120/208/1 PH.
8
6
0
0
8
6
30/2
3#10, #10G, 3/4"C
5,341
DMDF13
120/208/1 PH.
10
8
0
0
10
8
30/2
3#10, #10G, 3/4"C
6,753
DMDF14
120/208/1 PH.
16
14
0
0
16
14
30/2
3#10, #10G, 3/4"C
10,991
DMDF15
120/208/1 PH.
18
16
0
0
18
16
30/2
3#10, #10G, 3/4"C
12,408
62