134
4.2.22 Supply Office
4.2.22.1 These offices are used by the supply officers for
administration and training purposes. They should be located to have
a view of the unit storage and staging areas, possibly through a
window, sidelight or door light, since they have air conditioning and
the spaces around them do not. An exterior window overlooking the
service drive to the staging area, and any vehicle barrier, are also
desirable.
4.2.22.2 There is typically a GFGI safe in at least one supply office;
provide a floor anchor, similar to that in the arms vault at the
appropriate office(s).
4.2.22.3 Space Design Information
General/Code
Size 11 sq m (120 sf) each typical
Occupancy business
Occupancy count 1 person per single office; shared
offices -10
Architectural/Interiors
Minimum STC rating 40
Ceiling height 2600 mm (8'- 8")
Floor VCT ; carpet as an alternative
Base vinyl
Walls painted gyp board; painted CMU as an alternative
Ceiling suspended acoustical ceiling tile (ACT)
Trim coat tree; chair rail to protect walls
Lockset office
Mechanical
Heating, occupied 20 degrees C (68 F); maintained 13
degrees C (55 F)
Cooling, occupied 25 degrees C (78 F); maintained
ambient
Ventilation comply with ASHRAE 62
Electrical
Lighting 50 fc
Voice/data two telephone/data duplexes per workstation
Furniture
Similar to full-time offices above
Equipment
Verify if additional equipment required in some offices
Special features or considerations
UFC 4-171-05