4.2.23 Janitorial
4.2.23.1 Janitorial closets provide space, and plumbing, for the cleaning and
authorization may be distributed throughout larger or multistory buildings for
maintenance convenience.
4.2.23.2 Space Design Information
General/Code Size varies
Occupancy business
Occupancy count not occupied; typically 1 person per
300 sf
Architectural/Interiors
Minimum STC rating 40
Ceiling height
Floor sealed concrete
Base none
Walls painted gyp board; painted CMU as an alternative
Ceiling none; paint structure
Trim
Lockset storeroom
Mechanical
Heating passive, through transfer air
Cooling passive, through transfer air
Ventilation ventilate with exhaust at 10 air changes per
hour; maintain negative pressure
Electrical
Lighting 10 fc
Voice/data none
Furniture
Equipment
Mop hooks At least 3 lineal meters (10 ft) of shelving
Special features or considerations
Floor sink with spout with pail hook
Ordinary hazard sprinklers
4.2.24 Flammable Storage: These rooms are rarely provided in training
centers; see OMS Flammable Storage, Section 4.3.7 below.
4.2.25 Controlled Waste Storage: These rooms are rarely provided in
training centers; see OMS Controlled Waste Storage, Section 4.3.8 below.