111
4.2.6.3.3 In larger or multistory facilities, additional IT hub
rooms may be required to maintain compliance with the
restriction of 91 meters (300 ft) maximum for IT cable runs
beyond a hub. The minimum size for an IT hub room is 3050
mm by 4250 mm (10 ft by 14 ft).
4.2.6.3.4 Refer to the "USAR CIO Information Technology
Requirements for Military Construction Army Reserve" for the
specific size, equipment and furniture requirements of the IT
spaces.
4.2.6.3.5 Space Design Information
General/Code
Size varies
Occupancy business
Occupancy count 1 person per 9.3 sq m (100 sf)
Architectural/Interiors
Minimum STC rating 40
Ceiling height
Floor static-dissipative VCT
Base rubber
Walls painted gyp board
Ceiling exposed structure, painted
Trim coat hooks for work space; chair rail to protect
walls Lockset storeroom or classroom
Mechanical
Heating, occupied 20 degrees C (68 F); maintained
13 degrees C (55 F)
Cooling, occupied 25 degrees C (78 F); maintained
ambient
Ventilation comply with ASHRAE 62
Electrical
workstation
||content||
\ Furniture
ESD-type workbench with overhead shelving bins,
drawers, task light, power strip (plug-in type),
wrist connection and ESD working surface
ESD-type stool with arms
Optional freestanding metal desk-based workstation if
required. /1/
Equipment
Refer to criteria memo
Special features or considerations
Separate HVAC for equipment; size air conditioning
equipment for specific IT room requirements
UFC 4-171-05