148
Figure 4-33 Locker Room
4.2.41.2 Space Design Information
General/Code
Size varies
Occupancy business
Occupancy count 1 person per 9.3 sq m (100 sf)
Architectural/Interiors
Minimum STC rating 40
Ceiling height 2600 mm (8'- 8")
Floor ceramic tile
Base ceramic tile
Walls painted gyp board
Ceiling painted gyp board
Trim
Lockset classroom
Mechanical
Heating, occupied 20 degrees C (68 F); maintained
13 degrees C (55 F)
Cooling, occupied 25 degrees C (78 F); maintained
ambient
Ventilation Use 5 L/S/SQM in locker area and 10L/S/
SQM in shower areas; air pressure to be negative
Electrical
Voice/data wall phone
Furniture Equipment
Benches
Special features or considerations
4.2.42 Vending Alcove
4.2.42.1 This space is provided for vending machines for the
UFC 4-171-05