150
Minimum STC rating 40
Ceiling height 2600 mm (8'- 8")
Floor carpet; VCT as an alternative
Base rubber
Walls painted gyp board
Ceiling suspended acoustical ceiling tile (ACT)
Trim chair rail
Lockset passage
Mechanical
Heating, occupied 20 degrees C (68 F); maintained 13
degrees C (55 F)
Cooling, occupied 25 degrees C (78 F); maintained
ambient
Ventilation comply with ASHRAE 62; exhaust with local
Electrical
Lighting 50 fc
appliances; GFI duplex at sink
Voice/data wall-mounted phone
Furniture
Folding tables and stack chairs
Bulletin board
White board
Equipment Special features or considerations
Refrigerator and microwave are part of construction
contract
Counter with upper and lower cabinets and two-
compartment sink
Verify with Tenants if they will provide large coffeemaker
4.2.44 Mechanical
4.2.44.1 Mechanical space for HVAC equipment and ductwork will
be distributed through the building for efficient operation of the
mechanical systems.
4.2.44.2 The main mechanical space should have double doors to the
exterior for convenient access for maintenance and repair.
4.2.44.3 Space Design Information
General/Code
Size 8% times authorized bldg. functional area or as
required
Occupancy business
Occupancy count not occupied; typically 1 person per
27.9 sq m ( 300 sf)
UFC 4-171-05