155
4.3.1.3 NFPA 101 requires that no other spaces exit through the
workbays; if the office area requires two exits, an exit corridor must
be provided as well as a direct exit.
4.3.1.4 Access must be provided from the shop office to the workbay
area as well as to the exterior of the building.
4.3.1.5 Space Design Information
General/Code
Size varies
Occupancy business
Occupancy count 1 person per 9.3 sq m (100 sf)
Architectural/Interiors
Minimum STC rating 40
Ceiling height 2600 mm (8'- 8")
Floor VCT; carpet as an alternative in private offices
Base rubber
Walls painted gyp board; painted CMU as an alternative
Ceiling suspended acoustical ceiling tile (ACT)
Trim coat tree and chair rail
Lockset office or classroom
Mechanical
Heating, occupied 20 degrees C (68 F); maintained 13
degrees C (55 F)
Cooling, occupied 25 degrees C (78 F); maintained
ambient
Ventilation comply with ASHRAE 62
Electrical
Lighting 50 fc
Voice/data two voice/data duplexes at each workstation
Furniture
Same as full-time offices above no electrical within 475
mm (18 in) of floor
Equipment Special features or considerations
4.3.2 Unisex Toilet
4.3.2.1 The toilet authorization for the OMS is typically sufficient for
only one toilet. An accessible toilet is not required, due to an
exception in UFAS. Provide a urinal, toilet and sink.
4.3.2.2 Space Design Information: See Section 4.2.38 above.
4.3.3 Tools and Parts Storage Room
UFC 4-171-05