160
General/Code
Size varies
Occupancy high hazard storage
Occupancy count not occupied; typically 1 person per
27.9 sq m (300 sf)
Architectural/Interiors
Minimum STC rating 40
Ceiling height
Floor sealed concrete below metal grate
Base none
Walls painted CMU
Ceiling none; paint structure
Trim
Lockset entrance; code may require panic
Mechanical
Heating sufficient to avoid freezing
Cooling - none
Ventilation separate, continuous explosion-proof
ventilation interlocked with room lighting, or door
louvers
Electrical
Lighting 10 fc; minimum of two explosion-proof
fluorescents on exterior weatherproof pilot-lighted
exterior switch. Provide low temperature ballasts.
Voice/data none
Equipment
Open shelving
Special features or considerations
Extra hazard sprinklers; dry system in north
Open grating aluminum flooring over spill collection basin
4.3.9 Workbays
4.3.9.1 The workbay provides space for training and for the
performance of services and repairs of assigned equipment (mobile
and stationary). There are two basic types of workbay
configurations, single access and drive-through double access.
Drive-through workbays should be included whenever possible;
two workbays end to end, with an overhead door at the opposite
ends.
4.3.9.2 The workbays are the heart of the OMS. The other support
areas are normally located as closely adjacent to the workbays as
possible under the exiting requirements of NFPA 101; consider
locating most of them off a corridor into the workbay, with the other
UFC 4-171-05