163
4.3.10.2 Space Design Information
General/Code
Size varies
Occupancy low hazard storage
Occupancy count not occupied; typically 1 person per
27.9 sq m (300 sf)
Architectural/Interiors
Minimum STC rating 40
Ceiling height
Floor concrete
Base none
Walls painted CMU; painted gyp board as an alternative
Ceiling none; paint structure
Trim
Lockset entrance
Mechanical
Cooling none
NOTE: In climates exceeding 5000 degree days,
both underslab coils and overhead infrared radient
Electrical
Lighting 30 fc
Open shelving
Special features or considerations
Connections to flow switches, tamper switches, and fire
alarm
Power and data connections for computer if energy
management control system
Ordinary hazard sprinklers
Floor drains for relief valves, hose bibb, eyewash if water
treatment chemicals in room
Verify with Tenants any special connections for equipment
4.3.11 Information Technology
4.3.11.1 This space authorization is required to provide an IT hub for
the OMS, with connection typically back to the training center
network operations center. This may be part of a telephone room,
and is sometimes located within the shop office in an out-of- the-way
corner.
UFC 4-171-05