158
automated inventory
Voice/data wall voice receptacle; data receptacle if
automated inventory
Furniture
Equipment
Open shelving
Special features or considerations
Ordinary hazard sprinklers
4.3.5 Special Equipment Alcove
4.3.5.1 The Tenants typically have equipment such as tire changers,
balancers, etc., which is in frequent use, but cannot be located
within the maintenance bays. An authorization of 18.6 sq m (200 sf)
is provided to accommodate this equipment. The designer should
locate this alcove off the workbay area where this equipment can
be permanently located, convenient to the workbays and with
sufficient space for operation of the equipment.
4.3.5.2 Space Design Information: Refer to the space design
information for the workbays; this space is treated as an integral
part of the workbays, and the space design should be the same.
4.3.6 Battery Room
4.3.6.1 Battery rooms are no longer authorized for an OMS; for
exceptions, see information at Section 4.5.
4.3.7 Flammable Storage
4.3.7.1 This space is provided for storage of petroleum-based
lubricants, paints, solvents, etc. for use in the OMS. Due to the
volatile nature of the contents, it will have exterior access only, and
CMU wall to structure or a concrete ceiling.
4.3.7.2 The room should have a depressed well under a metal
grate floor for collection of any spills: no drain. The well should be
sloped to allow convenient suction of spills at a low point. The well
should be capable of containing 150% of the stored materials;
verify likely amount of stored materials with Tenants.
4.3.7.3 Some steel shelving is typically provided, with some floor
area left open for larger containers.
4.3.7.4 Space Design Information
General/Code
Size varies
UFC 4-171-05