164
4.3.11.2 Designer should coordinate the equipment requirements with
the AR Installation and Tenants.
4.3.11.3 Space Design Information
General/Code
Size 16 sq m (280 sf)
Occupancy business
Occupancy count not occupied; typically 1 person per
27.9 sq m (300 sf)
Architectural/Interiors
Minimum STC rating 40
Ceiling height
Floor VCT, static dissipative
Base rubber or vinyl
Walls painted gyp board
Ceiling exposed structure, painted
Trim
Lockset storeroom
Mechanical Heating, occupied 20
degrees C
(68 F);
maintained 13 degrees C (55 F)
Cooling to maintain suitable temperatures for equipment,
possibly continuous
Ventilation comply with ASHRAE 62
Electrical
Lighting 30 fc
Receptacles convenience duplexes; dedicated 20A circuits
for servers
Voice/data wall phone
Furniture
||content||
\ There is no furniture provided for this room function /1/
Equipment
Computer racks are part of the construction contract
LAN equipment and connections by the AR Installation
Special features or considerations
Some units have separate computer systems for OMS
operations
4.4
4.4.1 An unheated storage building is provided for storage of
Unheated
equipment and supplies that do not require a controlled climate.
Storage (UHS)
These buildings are typically simple pre-engineered metal buildings,
but may be designed to match other buildings in the facility if the
project budget allows. One or more personnel doors and one or
more overhead doors are typical; the standard overhead door size
is 2450 mm by 2450 mm (8 ft by 8 ft). These buildings are not
UFC 4-171-05