152
4.3
Architectural/Interiors
Organizational
Minimum STC rating 40
Maintenance
Ceiling height
Shop (OMS)
Floor concrete, sealed
Base none
Walls sealed and painted CMU; painted gyp board as an
alternative
Ceiling none, paint structure
Trim
Lockset storeroom
Mechanical
Heating, occupied 20 degrees C (68 F); maintained 13
degrees C (55 F)
Cooling none
Ventilation to maintain suitable temperatures for equipment
Electrical
Lighting 30 fc
Voice/data wall phone
Furniture Equipment
Electrical service equipment
Special features or considerations
Main ground bar
Ordinary hazard sprinkler
Avoid routing piping above electrical equipment
4.2.46 Telephone
4.2.46.1 The main telephone service room should also be a dedicated
space, not shared with mechanical or electrical equipment. This is the
utility service entrance, and the demarcation point between utility and
Government telephone system ownership.
4.2.46.2 Space Design Information
General/Code
Size 9.3 sq m (100 sf)
Occupancy business
Occupancy count not occupied; typically 1 person per
27.9 sq m (300 sf)
Architectural/Interiors
Minimum STC rating 40
Ceiling height
Floor concrete, sealed
Base none
Walls sealed and painted CMU; painted gyp board as an
alternative
Ceiling none, paint structure
UFC 4-171-05