121
4.2.11.11 For revitalization programs, modular arms vaults are
acceptable if they meet the criteria of Federal Specification AA-V-
737, Modular Vault Systems, and are approved by GSA. One
manufacturer of such vaults is CustomVault Corporation, Alexandria,
VA; their vaults must be installed in humidity-controlled
environments. A new floor may be required, depending on condition
of existing floor.
4.2.11.12 Space Design Information
General/Code
Size varies
Occupancy business
Occupancy count not occupied; typically 1 person per
300 sf
Architectural/Interiors
Minimum STC rating not applicable
Ceiling height 2500 mm (8'- 2") minimum
Floor sealed concrete
Base none
Walls painted concrete
Ceiling exposed structure, painted
Trim Lockset by vault door supplier
Mechanical
Cooling none
Ventilation 2.5 L/S/SQM thru transfer ducts; duct
openings must comply with AR 190-11
Electrical
Lighting 50 fc;
connection to IDS supervision
Furniture
||content||
\ There is no furniture provided for this room function /1/
Equipment
Special features or considerations
24-hour fluorescent, vandal-proof fixture outside vault
door, above door
Power, conduit and boxes for intrusion detection system
(IDS) by Government
Minimize penetrations in vault envelope
Tenants may want a Dutch door for weapons distribution
4.2.12 Armorer's Room
4.2.12.1 The armorer's room provides a space for weapons issue,
inspection, training, cleaning and repair.
UFC 4-171-05