4.2.12.2 If the arms vault door opens into the armorer's room, a
physical security light is required outside the armorer's room door -
see 4.2.11.6.
4.2.12.3 Space Design Information
General/Code
Size 9.3 sq m (100 sf)
Occupancy business
Occupancy count 1 person
Architectural/Interiors
Minimum STC rating 40
Ceiling height 2600 mm (8'- 8")
Floor -VCT
Base rubber
Walls painted gyp board
Ceiling suspended acoustical ceiling tile (ACT)
Trim
Lockset office
Mechanical
Heating, occupied 20 degrees C (68 F); maintained
13 degrees C (55 F)
Cooling, occupied 25 degrees C (78 F); maintained
ambient
Ventilation comply with ASHRAE 62
Electrical
duplexes
||content||
\ Furniture
Workbench with butcher block top and power strip (plug-in
type)
Stool with woven "Crypton" upholstery
Lockable storage cabinet
Equipment
There is no equipment provided for this room function /1/
Special features or considerations
Continuous 110 v power strip above the workbenches
4.2.13 Classrooms
4.2.13.1 This space is used primarily for instructional training of unit
personnel, but may also be used as a conference/meeting room on
occasion.
4.2.13.2 Classroom space authorizations are based on 0.75 sq m (8
sf) per person. If the authorization allows, some larger and some
smaller classrooms should be provided, with larger classrooms