127
4.2.16 Learning Center
4.2.16.1 This space is used as a computer training space. It
can be used for individual testing or group instruction.
4.2.16.2 Space Design Information
General/Code
Size varies
Occupancy business, unless 4.2.12.5 above governs
Occupancy count 1 person per 1.9 sq m (20 sf)
Architectural/Interiors
Minimum STC rating 40
Ceiling height 2600 mm (8'- 8")
Floor carpet; VCT as an alternative
Base rubber
Walls painted gyp board
Ceiling suspended acoustical ceiling tile (ACT)
Trim chair rail
Lockset classroom
Mechanical
Heating, occupied 20 degrees C (68 F); maintained 1 3
degrees C (55 F)
Cooling, occupied 25 degrees C (78 F); maintained
ambient
Ventilation comply with ASHRAE 62
Electrical
Lighting 50 fc
Voice/data telephone and data outlets
Furniture
Tables with c-legs on castors, wire management basket,
Table to be 9.14 m (30") deep and long enough to
accommodate 2 computers with three-ring binder
space between
Mid-back upholstered task chairs with adjustable arms
Height adjustable upholstered stool with arms
Combination lectern to hold computer, monitor and
keyboard connected to a projection screen
Lockable storage cabinet with shelves
TV/VCR cart, one (1) for every two (2) classrooms;
minimum one (1) per project; to be stored in training
aid storage rooms
UFC 4-171-05