UFC 1-300-09N
25 May 2005
9-6
FIRE PROTECTION SUBMITTALS.
This section summarizes the items required at each submittal stage for design-build
projects. Not all submittal stages are necessarily required. Contract documents will
outline which submittals are required and information presented below is a guide of the
minimum level of information required at each submittal stage.
9-6.1
Design Development Submittals.
9-6.1.1
Basis of Design. Complete Basis of Design meeting the requirements as
outlined throughout this guide.
9-6.1.2
Drawings. These drawings will not need to contain information on the
suppression and detection systems other than for coordination purposes.
9-6.1.3
Calculations.
Submit all hydraulic calculations supporting all fire suppression systems for the project.
Make all calculations using commercially available hydraulic sprinkler computer
software.
9-6.2
Pre-Final Design Submittals.
9-6.2.1
Basis of Design.
Complete final Basis of Design meeting the requirements as outlined throughout UFC 3-
600-10N.
9-6.2.2
Drawings.
Provide construction (shop) drawings for the suppression systems, detection and alarm
systems, firestopping, spray-applied fireproofing.
9-6.2.3
Calculations.
Submit complete final calculations supporting all the fire suppression systems for the
project. All calculations must be made using commercially available hydraulic sprinkler
computer software.
9-6.2.4
Specifications.
Specifications are not necessary for the suppression systems, detection and alarm
systems, firestopping, and spray-applied fireproofing. Provide manufacturer's data
sheets for these items.
56