UFC 1-300-09N
25 May 2005
Show locations of sprinkler risers, exterior water flow alarms, fire
department connections, post indicator valves, and back flow preventers.
Show the location of all isolation control valves. Do not show sprinkler branch
lines or feed main piping, unless a specific routing is required. i.e.: single feed
to computer room or elevator equipment room and hoistway.
Location of fire alarm and suppression system devices requiring 120V
power supply or greater. i.e.; fire alarm control panel, fire suppression system
control panel, fire suppression system air compressor, fire pump and jockey
pump controllers. Ensure power connections for fire pumps are in strict
compliance with NFPA 20, Standard for Installation of Stationary Pumps for
Fire Protection.
8-6.1.3
Calculations.
Submit all hydraulic calculations supporting all fire suppression systems for the project.
Make all calculations using commercially available hydraulic sprinkler computer
software.
8-6.1.4
Guide Specifications.
Provide an outline list of the required fire protection specifications supporting the
project.
8-6.2
Pre-Final Design Submittals.
8-6.2.1
Basis of Design.
Complete final Basis of Design meeting the requirements as outlined throughout this
guide.
8-6.2.2
Drawings.
Provide, as a minimum, all drawings as shown in the UFC 3-600-10N.
8-6.2.3
Calculations.
Submit complete final calculations supporting all the fire suppression systems for the
project. Make all calculations using commercially available hydraulic sprinkler computer
software.
8-6.2.4
Specifications.
Provide full edited fire protection specifications supporting the project.
8-6.3
Final Design Submittals.
8-6.3.1
Drawings.
41